5.6 Additional parameters
BU 0500 GB Subject to technical alterations 105
Parameter Set value / Description / Note Device Supervisor
Parameter
set
P510 ... - 01
... - 02
Setpoint source
S
Selection of the setpoint source to be parameterised.
[01] = Master setpoint value source [02] = Auxiliary setpoint value source
Selection of the interface via which the FI receives the setpoint.
0 ... 10
[ 0 ]
0 = Auto: The source of the auxiliary setpoint is
automatically derived from the setting in the parameter
P509 >Interface<
1 = Control terminals, digital and analog inputs control the
frequency, including fixed frequencies
2 = USS
3 = CAN
4 = Profibus
5 = InterBus
6 = CANopen
7 = DeviceNet
8 = reserved
9 = CAN Broadcast
10 = CANopen Broadcast
P511 USS Baud rate
S
Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must
have the same baud rate setting.
0 ... 3
[ 3 ]
0 = 4800 baud
1 = 9600 baud
2 = 19200 baud
3 = 38400 baud
P512 USS address
0 ... 30
[ 0 ]
Setting the FI Bus address.
P513 Telegram down time
S
-0.1 / 0.0 /
0.1 ... 100.0 s
[ 0.0 ]
Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one
must arrive within the set period. Otherwise the FI reports an error and switches off with the error
message E010 >Bus Time Out<.
0.0 = Off: Monitoring is switched off.
-0.1 = no error: Even if communication between BusBox and FI is interrupted (e.g. 24V error, Box
removed, etc.), the FI will continue to operate unchanged.
P514 CAN Baud rate
Used to set the transfer rate (transfer speed) via the CANbus interface. All bus participants must
have the same baud rate setting.
Additional information is contained in the manual BU 0060 CAN/CANopen.
0 = 10kBaud
1 = 20kBaud
2 = 50kBaud
3 = 100kBaud
4 = 125kBaud
5 = 250kBaud
6 = 500kBaud
7 = 1Mbaud * (test
purposes only)
0 ... 7
[ 4 ]
*) Safe operation cannot be guaranteed
P515 ... - 01
... - 03
CAN address
Setting for the CANbus address.
From SW 1.6 and above, can be set in three levels:
0 ... 255
[ 50 ]
[01] = Receipt address for CAN and CANopen (as before)
[02] = Broadcast – receipt address for CANopen (Slave)
[03] = Broadcast –Transmission address for CANopen (Master)