EasyManua.ls Logo

nord sk 200e - Page 6

nord sk 200e
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.nord.com
4
Bayer SK200E Troubleshooting Guide – Subject to Change Without Notice
SK 072.1F-71/S4
Motor Mounted SK 200E
Initial Checks – Pump Drive Ctd.
3) CheckACpowerconnections
a.Mains supply voltage must be 200-240VAC,
single-phase. Mains supply voltage must be
connected directly to terminals L1 & N (see
Figure5).Earthgroundisconnectedtooneof
thetwoPEterminals.
b.Confirmmotorleadsareconnectedtoterminals
U-V-W(seeFigure5).
c.Confirmthatthemotoriswiredforlowvoltage,
230VAC (see Figure 6). If motor jumpers
(beneaththeclearplasticbarrier)areconnected
differently,eitherthemotorjumpershavetobe
set as shown, or the motor/drive has to be
replaced.
4) ChecktheM12receptacleandinternalcontrolwiring
a.Confirm that the M12 receptacle is wired per
thediagramshowninFigure10.Ifanyofthe
wires are incorrectly landed, make necessary
changes.Also,ensurethatthewiresaresecurely
fastenedandtheterminalsarescrewedtightly.
b.Figure 10 also shows the pinout of the M12
receptacle. Confirm that the mating cable
receptaclehasamatchingpinout.
5) CheckdriveDIPswitchsettings(seeFigure8).DIP
switch settings other than discussed below may
resultinimproperoperation.
a.FromtheNordfactory,DIPswitch7isturnedon
toconfigurethedrivefora60Hzmotor.
6) Once items 1-5 have been performed, the drive
may be mounted on the motor adapter again.
Lineupthecinchplugsandtightenthe4mmhex
sockethead screws. Input AC power may be
appliedatthistime.
Figure 5 - Motor Terminal Block
U V W
Figure 6 - Motor Power Connections
Figure 7 - Control Wiring Connections
Figure 8 - DIP Switch Settings

Related product manuals