Bayer SK200E Troubleshooting Guide – Subject to Change Without Notice
Programming
Programming
TheSK 200EAC vectordriveisconguredfrom the
factorywithaspecicparametersetforOnDemand™
applications. Table 1 shows the critical parameters
thatmustbesetproperlyforthisapplication.Only
thevaluesinparameterset1(P1)areimportant.Pa-
rametersetsP2,P3,andP4maybeignored.
Table 1 – SK 205E Parameter Settings
Param. # Param. Name Setting
P102 AccelerationTime 1.00 s
P103 DecelerationTime 1.00 s
P105 MaximumFrequency 100.0Hz
P201 NominalFrequency 60Hz
P202 NominalSpeed 1710rpm
P203 NominalCurrent 1.6A
P204 NominalVoltage 230V
P205 NominalPower 0.25 kW
P206 Cos Phi 0.64
P207 Stardeltacon. Star
P2081 StatorResistance ~10.0 Ω
P402[-05] AnalogInputAdj.0% 1.00V
P403[-05] AnalogInputAdj.100% 5.00V
P420[-02] DigitalInput2 03:Phaseseq.reversal
P434[-01] DigitalOutput1 2:Inverterisworking
P505 Absoluteminifreq. 1.0Hz
P509 SourceControlWord 0:Contrtermorkeyb
P510 SourceSetpoint 0:Auto
Note 1: Stator resistance setting will vary on each unit.
Setting must be 10.0 Ω, ±15%.
Parameters may be accessed with the use of a lap-
top,NORDCONsoftware,andappropriatecables.Al-
ternatively,theSKPAR-3Hhand-heldparameterbox
mayalsobeused.Thecablesinterfacewiththedrive
viatheRJ12portinthediagnosticcockpits(seeFig-
ure 11). If the settings of the drive are not similar
tothoseinTable1,thedrive/motormaynotperform
properly.
Figure 9 - NORDCON Screenshot
Refer to operating manual BU0040 for additional
informationonaccessing the parametersviathe SK
PAR-3Hparameterbox.