Control System Settings
B-2
Part 1123087_02
3/2014 Nordson Corporation
Master Controls: Settings Screen
Master Controls: Settings Screen
Button/Menu Item Default
Range of Values or
Optional Settings
Heater Control — On (See Note A) Off
Standby — Off On
Pump Control — Off On
Scheduler — Off On
Refill — Enabled Disabled
Temperature
Smart Melt Enabled Disabled
Global Setpoint 175 C (350 F) 40-204 C (100-400 F)
Smart Melt Temperature 15 C (25 F)
0-30 °C (0-60 °F)
Temperature Limits Overtemperature:
15 C (25 F)
Undertemperature:
25 C (50 F)
5-60 C (10-110 F)
Global Temperature
Change
+/-1 °C (+/-1 °F)
—
Smart Melt Time 10 (minutes) 5-60 (minutes)
Fill
Fill Flutter Delay 5 (seconds) 0-1200 (seconds)
Overfill Delay 60 (seconds) 10-300 (seconds)
Audible Fill Alarm Enabled Disabled
Alert to Fault Delay Time 4 (minutes) 1-20 (minutes)
Inputs
Input 1
Automatic Standby
(available for input 1 only)
Disabled
Standby
Heater Control
Pump Control
External Zone 1A/1B
External Zone 2A/2B
Automatic Standby
(available for input 1
only)
Fill Enable/Disable
Input 2
Standby
Input 3
Heater Control
Input 4
External Zone 1A/1B
Ready Delay — 0 (minutes) 0-60 (minutes)
NOTE A: The first time the melter is switched on after a factory reset, Heater Control is Off. For all other times the
melter is switched on, Heater Control is On, regardless of whether it was On or Off when the melter was
switched off.
Continued...