Operating Parameters
B-7
Part 1120277_01
E 2012 Nordson Corporation
Pressure Control
15 Pressure Setpoint
Description: Used to set the percentage of maximum output pressure (from
0-100 percent).
Value: 0 to 100 (percent)
Resolution:
Default Value: 0(disabled)
Format:
Use: This parameter is available only when the optional analog
input/output (I/O) board is installed on the melter. Refer to
Section 7, Parts, for the I/O board kit part number. The pressure
is displayed after the last gun temperature: the left display
shows a P (for pressure) and the right display shows the
pressure reading.
16 Over Pressure Setpoint
Description: If the pressure in the s ystem exceed s the value of this setting, an
over-pressure alarm will occur.
Value: 0 to 50 (percent) above the pressure s etpoint (parameter 15)
Resolution:
Default Value: 0
Format:
Use: This parameter is available only when the optional analog I/O
board is installed on the melter. R efer to Section 7, Parts,forthe
I/O board kit part number.
17 Under Pressure Setpoint
Description: If the pressure in the s ystem drops below the value of this
setting, an under-pressure alarm will occur.
Value: 0 to 50 (percent) below the pressure setpoint (parameter 15)
Resolution:
Default Value: 0
Format:
Use: This parameter is available only when the optional analog I/O
board is installed on the melter. R efer to Section 7, Parts,forthe
I/O board kit part number.