Installation
3-11
Part 1120277_01
E 2012 Nordson Corporation
Configuring the Electrical Service
PURBlue 4 melters are shipped from the factory without an attached power
cable and without a designated service-type. To configure the melter to
function in your facility, you must connect a power cable to the melter and
designate the service type by installing a Nordson-supplied voltage plug into
the melter.
To connect a power cable to the melter
WARNING! Risk of electrocution! Install a lockable power disconnect switch
between the electrical service and the melter. Failure to install or properly
use the disconnect switch when servicing the melter can result i n personal
injury, including death.
1. Select a 10 mm
2
(8 AWG) power cable that meets applicable electrical
codes and standards. The maximum amperages of P URBlue 4 melters
operating at a specified voltage are shown in Table 3-2.
Table 3-2 Maximum Amperages
Model Voltage (VAC) Maximum Amperage
PURBlue 4,
three hoses/guns
200-240, 1-phase
20-25
200-240, 3-phase
18-22
400/230Y, 1-phase
24
400/230Y, 3-phase
15
NOTE: The voltage tolerance is 10 percent. For 200-240 VAC systems,
the voltage must be 180-264 VAC.