Typical voltage plugs
(plugs with and without the neutral
lead shown)
Installation
3-14
Part 1120277_01
E 2012 Nordson Corporation
To connect a voltage plug to the melter
1. Refer to Table 3-3 to determine the part number of the voltage plug that
matches the required electrical service. Each voltage plug is labeled with
its part number and service type.
SeeFigure3-5.
2. Insert the correct voltage plug into receptacle X1. Ensure that the plug
snaps into place. If the plug contains a neutral lead, connect the neutral
lead to receptacle X2.
3. When the electrical service is completely installed and inspected in
accordance with local electrical codes and standards, close the electrical
enclosure door and switch the local power disconnect switch on.
If the electrical service was configured correctly, the melter control panel
will display dashes.
X2
X1
X1
P/N 232617
P/N 227569
P/N 227567
P/N 227568
Figure 3-5 Connecting a voltage plug