DC Inverter U-match Series Floor Ceiling Type Unit
Table 3.3
mm (inch)
Max.
Pipe
Length
m (feet)
Max. Height
Difference
between Indoor
Unit and Outdoor
Unit
pipe(Out
thickness)
mm (inch)
GFU18(5.3)USV4DH
GXH18(5.3)USV4DH
15(49)
Φ17X1.75
GFU24(7.0)USV4DH
GXH24(7.0)USV4DH
15(49)
Φ17X1.75
GFU30(8.8)USV4DH
GXH30(8.8)USV4DH
15(49)
Φ17X1.75
GFU36(10.6)USV4DH
GXH36(10.6)USV4DH
15(49)
Φ17X1.75
GFU42(12.3)USV4DH
GXH42(12.3)USV4DH
15(49)
Φ17X1.75
GFU48(14.1)USV4DH
GXH48(14.1)USV4DH
15(49)
Φ17X1.75
Notes:
ķ
.
The connecting pipe should be thermally insulated.
ĸ
.
The pipe wall thickness shall be 0.5~1.0mm (0.02~0.04inch) and the pipe
wall shall be able to withstand the pressure of 6.0MPa (870psig). The
shorter the connecting pipe, the better the cooling and heating effect.
3.4 Electrical Requirement
Electric Wire Size and Fuse Capacity.
Table 3.4
Indoor Units
Ampacity
Over