Table F3: Compressor Run Load Amperage (RLA)
Compressor
Tonnage
Cooling Type
Voltage
208/230/1/60 208/230/3/60 460/3/60 575/3/60
Air Cooled Single Circuit
2
On/off 12.8 8.3 5.1 3.3
Two-stage 15.3 11.6 5.7 4.0
3
On/off 17.9 13.5 7.1 4.9
Two-stage 17.9 14.2 6.2
4
On/off 25.0 15.9 7.1 5.1
Two-stage 28.8 16.2 7.6
5
On/Off 28.3 19.0 9.7 7.4
VRC 20.4 9.7
6
On/off 23.2 11.2 7.4
VRC 23.2 11.2
8
On/off 29.5 14.7 7.9
VRC 24.0 12.6
10
On/off 33.3 17.9 12.8
VRC 33.3 17.9 12.8
12
On/off 48.1 18.6 14.7
VRC 48.1 18.6 14.7
14
On/off 51.3 23.1 19.9
VRC 51.3 23.1 19.9
16
On/off 55.8 26.9 23.7
VRC 55.8 26.9 23.7
21
On/off 30.4 24.6
VRC
Air Cooled Dual Circuit
6
On/off 13.5 6.0 4.9
VRC 16.1 7.8
8
On/off 15.9 7.1 5.1
VRC 17.9 7.8
10
On/off 19.0 9.7 7.4
VRC 20.4 9.7
12
On/off 23.2 11.2 7.9
VRC 23.2 11.2
14
On/off 25.0 12.2 9.0
VRC 24.0 12.6
16
On/off 29.5 14.7 12.2
VRC 24.0 12.6
21
On/off 33.3 17.9 12.8
VRC 33.3 17.9 12.8
Shaded areas indicate unavailable compressor selection.
Values indicated are for single compressor only.
VCES-VHC-IOM-1F – VHC-36, -42 & -50
39