Appendix S: Temperature Rise Over Gas-fired Furnace
Table S1: VHC-36 Temperature Rise Over Gas-fired Furnace (°F) – 5:1, 2:1 and On/Off Models
Air Volume (CFM) 100 MBH 125 MBH 200 MBH
800 94.1
900 83.6
1,000 75.2 94.1
1,100 68.4 85.5
1,200 62.7 78.4
1,300 57.9 72.3
1,400 53.7 67.2
1,500 50.2 62.7 100.3
1,600 47.0 58.8 94.1
1,700 44.3 55.3 88.5
1,800 41.8 52.3 83.6
1,900 39.6 49.5 79.2
2,000 37.6 47.0 75.2
2,100 35.8 44.8 71.7
2,200 34.2 42.8 68.4
2,300 32.7 40.9 65.4
2,400 31.4 39.2 62.7
2,500 30.1 37.6 60.2
Table S2: VHC-42 Temperature Rise Over Gas-fired Furnace (°F) – 5:1, 2:1 and On/Off Models
Air Volume (CFM) 200 MBH 250 MBH 300 MBH 350 MBH
1,500
1,600 94.1
1,700 88.5
1,800 83.6
1,900 79.2
2,000 75.2 94.1
2,100 71.7 89.6
2,200 68.4 85.5
2,300 65.4 81.8
2,400 62.7 78.4 94.1
2,500 60.2 75.2 90.3
2,600 57.9 72.3 86.8
2,700 55.7 69.7 83.6
2,800 53.7 67.2 80.6 94.1
2,900 51.9 64.9 77.8 90.8
3,000 50.2 62.7 75.2 87.8
3,100 48.5 60.7 72.8 84.9
3,200 47.0 58.8 70.5 82.3
3,300 45.6 57.0 68.4 79.8
3,400 44.3 55.3 68.4 77.5
3,500 43.0 53.7 64.5 75.2
Notes for the above tables:
Use caution in shaded areas.
Values above are calculated at sea level.
Temperature rise = Sea level temperature rise / (1−Elevation (ft.) x 0.0000334)
Gas inlet pressure required for natural gas minimum 5” w.c., maximum 13.5” w.c.; for propane minimum 11” w.c., maximum 13.5” w.c.