8. More Advanced Function
— 8-17 —
The output closes when the Motor position data is in the set zone.
When the Motor passes the zone with high speed or when the zone is too narrow, the zone
passage time gets short. The parameter ZAW (Zone passage stability timer) is available to set
the minimum time width for detecting the passage.
Fig 8-7: Example: Signal timing of the output ZONEA
The outputs ZONE (In-zone) do not function in the middle of Home Return.
8.3.2. Outputs of Operating Conditions
The outputs report the Motor conditions against the thresholds.
The table below lists available outputs.
Table 8-16: Outputs for Motor conditions
Logic (In case of positive logic)
Tell position error, under
Reports the condition of position
error
Open: Not activated,
Closed: Position error is less or equal to the
setting of parameter TEU.
Tell position error, over
Open: not activated.
Closed: Position error is greater or equal to
the setting of parameter TEO.
Tell velocity error, under
Reports the condition of current
velocity error.
Open: Not activated.
Closed: Current position is less or equal to
the setting of parameter TVEU.
Tell velocity error. over
Open: Not activated.
Closed: Current position is greater or equal to
the setting of parameter TVEO.
Reports the condition of current
velocity.
Open: Not activated.
Closed: Current position is less or equal to
the setting of parameter TVU.
Open: Not activated.
Closed: Current position is greater or equal to
the setting of parameter TVO.
Tell torque command,
under
Reports the condition of torque
command.
Open: Not activated.
Closed: Torque command is less or equal to
the setting of parameter TTU.
Tell torque command, over
Not activated.
Closed: Torque command is greater or equal
to the setting of parameter TTO.
Tell thermal loading, under
Reports the condition of thermal
loading.
Open: Not activated.
Closed: Thermal loading is less or equal to
the setting of parameter TJU.
Tell thermal loading, over
Open: Not activated.
Closed: Thermal loading is greater or equal to
the setting of parameter TJO.