14-4
14.2. Description of Alarm
Caution : The DRDY output is normally closed. It opens on abnormal condition.
14.2.1. Normal State
l When the Motor does not operate even in normal state, following causes are suspected.
Table 14-2
Status Motor condition DRDY Cause Remedy
Power-off Servo-OFF open Power is not supplied. Turn on power.
CPU Initializing Servo-OFF open Initializing the CPU. Wait for the CPU to be initialized.
SVON Input OFF Servo-OFF close SVON input is not active. Activate the SVON input.
14.2.2. Alarms Related to Power Amplifier
14.2.2.1. Heat Sink Overheat or Regeneration Resistor Overheat
[Output] DRDY: Open
[TA] P0 > Over Heat
[LED] P0
[Motor Condition] Servo-OFF
Table 14-3: Cause and Remedy: Overheat of heat sink and regeneration resistor.
Cause Remedy
(1) Duty cycles of the Motor is too high.
(2) Excessive load is applied.
Reduce the load and/or operation duty. Readjust
acceleration/deceleration.
(Stop operation, air-cool the Driver Unit.)
(3) Ambient temperature is above 50°C.
(4) Heat sink temperature exceeds 90°C due to
continued heavy torque demand.
Check surrounding condition of the Driver Unit.
Stop the operation and air-cool the Motor and Driver
Unit. Then check followings.
Whether the duty cycle is too high.
Whether excessive load is applied.
If the ambient temperature of the Driver Unit is
too high.
If no troubles are found in the above check and this
alarm occurs frequently, contact NSK.
(5) Defective PCB.
(As soon as the control power is turned on,
the alarm is activated.)
Replace Driver Unit.
Standard ESA Driver--------------------[Appendix 4]
Note : 1) Stop operation immediately.
2) Even the alarm is deactivated, it will be activated again when the thermal sensor is still
on.
• Take enough time to air-cool the Motor and the Driver Unit.