3.2. Technical data
Product application
nVent RAYCHEM Pipe freeze protection heating
cables only
Electrical properties
Supply voltage 180-253 VAC; 50/60Hz
Power consumption 5,3 W max
Power output relay
(heating cable)
25 A / 230 VAC
Power supply terminals 3 x 6 mm² max
Heating cable terminals 3 x 6 mm² max
Alarm terminals 3 x 1,5 mm² max
Sensor terminal - Pipe 2 x 1,5 mm² max
Alarm relay
Single pole double throw relay, volt-free;
Max. switching capacity (resistive load only)
1 A/30 VDC 0.5 A/125 VAC, Max.: 60 VDC/
125 VAC
Settings All settings are stored in non-volatile memory
Operating temperature –40°C to +40°C ambient
Selectable temperature
PiPE: 0°C ... +90°C
(PT 100 Sensor Module: –40°C ... +250°C:
SM-PT100-1; PCN: 1244-022441)
Air (PASC): 0°C ... +30°C
Enclosure
Material Polycarbonate
Dimensions 210 mm x 90 mm x 85 mm
Ingress protection class IP 65
Weight 990 g
Mounting DIN-Rail mountable 35 mm
Entries 2 x M25 and 2 x M20
Storage temperature –40°C to +50°C
Flammability class D category (DIN EN 60730/VDE 0631-1)
Sensor
Temperature sensor type Standard NTC 2,0 kOhm at 25°C, 2 wires
Sensor tip dimensions Ø 5 mm; length 20 mm
Sensor cable length 5 m; extendable up to 150 m , 2 x1,5 mm²
Temperature range –40°C to +90°C