Revision C (12/18)
3
Technical Specifications
Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire
(Delta)
90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III.
Two independent voltage reference inputs
48 channels, 0.525 VAC max, 333 mV CTs, 0-4,000+Amps depending on current
transducer
150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A
with RōCoil CTs.
True RMS using high-speed digital signal processing (DSP) with continuous sampling
From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max
Use of 12 volt auxiliary output requires 100 VAC minimum input voltage.
0.5A Fuse 200kA interrupt capacity
Unregulated 12VDC output, 200 mA, self-resetting fuse
Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received)
kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered)
kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD,
Theta, Frequency. All parameters for each phase and system total.
0.2% ANSI C12.20-2010 Class 0.2
Values reported in IEEE-754 single precision floating point format (32 bit).
4-line display, tri-color backlight (PhaseChek™)
AMC12 – 4 inputs, AMC48 – 2 inputs
Voltage Phase Loss Alarm (SPDT Relay - 30 VDC) ( only)
RS-485, Ethernet, & USB (for configuration only)
Modbus RTU or BACnet Master Slave Token Passing protocol (MS/TP)
Modbus (using SunSpec IEEE-754 single precision floating point model)
BACnet MS/TP
Modbus TCP
BACnet IP
Max Communication
Length (RS485)
1200 meters total cable length, with Data Range of 100K bits/second or less