UNICO ART R410A
EN - 13
ENGLISH
• Drilltheholesforanchoringthewallxingbracketusingthe4holesattheendsofthebracketasindi-
catedonthedrillingtemplateasarstpossibility(g.6).
• Ifthewallisofpoorconsistency,itisadvisabletousealargernumberofxinganchors.
Thebracketoffersmultiplepossibilitiesbothinthenumberofxingsandintheirposition.
• Thegreaterweightoftheapplianceisontheright,thereforeitispreferabletoensureamoresolidxing
from this side.
Carefully check the characteristics and consistency of the wall in order to possibly choose wall
plugs specic for particular situations.
The manufacturer will not be held liable for any underestimates made in the
structural consistency of the anchor prepared by the installer.
Therefore, pay utmost attention to the foregoing operation that could cause
serious injury/damage to people/property if carried out incorrectly.
• When installing models equipped with heating pump, if no condensate discharge was built into the wall
(seeparagraph2.4.2),inordertodrainthecondensateitwillbenecessarytodrillaholethroughthe
wall in the position shown on the template.
2.4.2 - Preparing the condensate discharge
• Asregardsmachineswithheatpump,acondensationdrainpipe(g.1-ref.N)(supplied)tobeinserted
inthespecicconnection(A)(g.7).
Removethecap(B)(g.7)beforeinsertingthecondensationdrainpipe.
Whenthemaxlevelisreached,asolenoidvalveensuresthecondensatewillowoutfromtheinternal
tray.
• For cold-only machines, connect the condensate discharge pipe if you intend running the unit at low
outdoortemperatures(lowerthan23°C).
• Since condensate drains by gravity, there must be a minimum slope of at least 3% at every point of the
dischargeline.Usearigidorexibletubehavinganinsidediameterofatleast16mm.
• If the line empties into a sewerage system, install a siphon before the point in which the pipe reaches
themaindischarge,atleast300mmbelowtheinletfromtheunit(g.8).
• Ifthedrainpipedrainsintoavessel(tankorothercontainer),thiscontainershouldnotbesealedand
thedrainpipeshouldnotremainimmersedinthewater(seeg.9).
• Theholethroughwhichthecondensatepipepassesshouldalwaysslopetowardstheoutside(seeg.
10).
The exact position in which to place the pipe inlet, as compared to the machine, is shown on the drilling
template.
Make sure, in this case, that the water expelled outward does not damage or
disturb persons or property.
During the winter this type of drainage may cause sheets of ice to form.