Reference Section: Initialization Mode (INIt)
Navigate to the desired setting. Settings include the following:
• 8bIt – 8 bits used per data character (factory default)
• 8bIt – 7 bits used per data character
Select the indicated option.
4.4.3.5 Stop Bits (INIt > CoMM > SER > C.PAR > StoP)
Select the number of Stop Bits (StoP).
Navigate to the desired setting. Settings include the following:
• 1bIt – 1 stop bit (factory default)
• 2bIt – 2 stop bits (provides a “force 1” parity bit)
Select the indicated option.
4.5 Safety Features (INIt > SFty)
Select Safety Features (SFty).
Navigate to the desired parameter. Parameters include the following:
• PwoN – Requires confirmation before running automatically at startup
• oPER – User must select RUN when exiting from the Stby, PAUS, or StoP Modes
• SP.LM – Setpoint limits can be set to limit the values that can be entered
• LPbk – Loop break enable/disable and timeout value
• o.CRk – Open circuit detection enable/disable
Select the indicated option.
4.5.1 Power On Confirmation (INIt > SFty > PwoN)
Select Power On Confirmation (PwoN).
Navigate to the desired setting. Settings include the following:
• dSbL – Program runs automatically at startup (factory default)
• ENbL – The unit powers on and then displays RUN; press the ENTER button to run
the program
Select the desired setting.
4.5.2 Operating Mode Confirmation (INIt > SFty > oPER)
Select the Operating Mode Confirmation (oPER) parameter.
Navigate to the desired setting. Settings include the following:
• dSbL – Pressing the ENTER button in Stby, PAUS, or StoP Modes will start running
the current program immediately (factory default)
• ENbL – Pressing the ENTER button in any Operating Menu Mode will display RUN;
pressing the ENTER button again will start running the current program
Select the desired setting.
4.5.3 Setpoint Limits (INIt > SFty > SP.LM)
Select Setpoint Limits (SP.LM) to set limits on the values that can be used for the all Setpoints.