PLATINUM
TM
Series User’s Guide
Reference Section: Programming Mode (PRoG)
Setting Absolute (AbSo) Deviation (d.SP1) Deviation (d.SP2)
< SP1 - ALR.L or > SP1 + ALR.H
< SP2 - ALR.L or > SP2 + ALR.H
> SP1 - ALR.L and < SP1 + ALR.H
> SP2 - ALR.L and < SP2 + ALR.H
Table 5.1 – Alarm Range Option Comparison
Absolute Mode (AbSo)
Deviation Mode (dEVI)
Figure 5.1 – Alarm Range Option Diagram
5.3.2 Absolute or Deviation Alarm (PRoG > ALM.1, ALM.2 > tyPE >
Ab.dV)
Select the Absolute or Deviation Alarm (Ab.dV) parameter.
Navigate to the correct setting. Settings and subsettings include the following:
• AbSo – Alarm is triggered using calculations based on the absolute values of ALR.H
or ALR.L used as specified by the tyPE parameter
• d.SP1 – Alarm is triggered using calculations based on values relative to SP1 as
specified by the tyPE parameter
• d.SP2 – Alarm is triggered using calculations based on values relative to SP2 as
specified by the tyPE parameter
Select the desired setting.
5.3.3 Alarm High Reference (PRoG > ALM.1, ALM.2 > tyPE >
ALR.H)
Select the Alarm High Reference (ALR.H) parameter.
Set the Alarm High Reference value.
5.3.4 Alarm Low Reference (PRoG > ALM.1, ALM.2 > tyPE > ALR.L)
Select the Alarm Low Reference (ALR.L) parameter.
Set the Alarm Low Reference value.
(SP2 has the same
alarm options.)
Omega Engineering | www.omega.com