Reference Section: Programming Mode (PRoG)
5.4 Output Channel 1–3 Configuration (PRoG > oUt.1oUt.3)
Navigate to the desired output channel. The number and type of output channels on the
PLATINUM
TM
Series are automatically recognized by the device. The following output names
are what you can see on the panel display replacing the generic oUt.1 through oUt.3
references used in this document:
StR1 Single Throw Mechanical Relay number 1
StR2 Single Throw Mechanical Relay number 2
dtR1 Double Throw Mechanical Relay number 1
dtR2 Double Throw Mechanical Relay number 2
SSR1 Solid State Relay number 1
SSR2 Solid State Relay number 2
dC1 DC Pulse output number 1
dC2 DC Pulse output number 2
dC3 DC Pulse output number 3
ANG1 Analog output number 1
ANG2 Analog output number 2
Note: All output channels have the same menu structure. However, only those parameters
that apply for the type of output being configured appear in that output’s menu.
Select the indicated output channel.
Navigate to the desired submenu. Submenus include the following:
ModE Allows the output to be set up as a control, Alarm, retransmission, or
Ramp/Soak event output; the output can also be turned off
CyCL PWM pulse width setting for DC pulse, mechanical relay, and solid state
relay outputs
RNGE Sets the Voltage or current range for analog outputs
Select the indicated setting.
5.4.1 Output Channel Mode (PRoG > oUt1oUt3 > ModE)
Select Output Channel Mode (ModE) to configure the specified output.
Navigate to the desired setting. Settings include the following:
oFF Turn off the output channel (factory default)
PId Set the output to Proportional-Integral-Derivative (PID) Control Mode
oN.oF Set the output to On/Off Control Mode
ALM.1 Set the output to be an Alarm using the ALM.1 configuration
ALM.2 Set the output to be an Alarm using the ALM.2 configuration
RtRN Set up the output for Retransmission
RE.oN Turns on the output during Ramp events
SE.oN Turns on the output during Soak events
Select the indicated setting.