Chapter 5
5-7
Remote I/O Functions
4.Click the Connection Tab of the Advanced Setting Window and select User Setup.
5.Select Use Poll Connection and Use COS connection.
6.Set Extended Control Status (Control I/O remote I/O) for the IN data and Extended Control Com-
mand (Control I/O remote I/O) for the OUT data as the poll connection’s connection paths.
7.Set Unit Status for the IN data as the COS connection’s connection path.
Note When a CS/CJ-series DeviceNet (Master) Unit is being used, set the COS connection’s OUT
data to the same setting set for the poll connection’s OUT data. If the connection paths do not
match, it will not be possible to select both Use Poll Connection and Use COS Connection.
Reference
The following connection path settings will be allocated automatically if you select the connection but
leave the connection path settings blank.
8.Click the OK Button to close the Advanced Settings Window.
Connection OUT (PLC Inverter) IN (PLC Inverter)
Poll Slave’s default connection path setting Slave’s default connection path setting
Bit-strobe Not allocated. Slave’s default connection path setting
COS Not allocated. Unit Status 154 decimal (9A hex)
Cyclic Not allocated. Unit Status 154 decimal (9A hex)