Chapter 6
6-14
Message Communications
01
07 Speed Actual
Rotational
Speed Monitor
(See notes 2
and 4.)
The output frequency
monitor (U-02/U1-02) can
be monitored in hexadeci-
mal with the minimum unit
as 1 hex.
The frequency monitor’s
minimum unit can be set
by the frequency refer-
ence setting and display
units in n035/o1-03.
n035/o1-03 = 0: 0.01 Hz
n035/o1-03 = 1: 0.01%
(100%: Max. frequency.)
n035/o1-03 = 2 to 39:
1r/min
n035/o1-03 = 40 to 3,999:
Follow individual set val-
ues.
When r/min units are
being used, a multiplier
can be set in attribute 16
(the Speed Scale setting).
--- 0000 Yes No Word
08 Speed Refer-
ence
Rotational
Speed Refer-
ence
(See notes 2
and 4.)
Can be set and read in
hexadecimal with the fre-
quency reference mini-
mum unit as 1 hex.
The frequency reference
minimum unit can be set
by the frequency refer-
ence setting and display
units in n035/o1-03.
n035/o1-03 = 0: 0.01 Hz
n035/o1-03 = 1: 0.01%
(100%: Max. frequency.)
n035/o1-03 = 2 to 39:
1r/min
n035/o1-03 = 40 to 3,999:
Follow individual set val-
ues.
When r/min units are
being used, a multiplier
can be set in attribute 16
(the Speed Scale setting).
0 to max. fre-
quency
0000 Yes Yes Word
09 Current Actual Can be referenced in
hexadecimal with the out-
put current monitor U-03/
U1-03 minimum unit as
0.1 A.
Setting the attribute 17
current scale enables a
multiplication factor to be
set.
--- 0000 Yes No Word
0F Power Actual Can be referenced in
hexadecimal with the out-
put power monitor U-11/
U1-08 minimum unit as
1W.
Setting the attribute 1A
power scale enables a
multiplication factor to be
set.
--- 0000 Yes No Word
Instance Attribute Name Content Setting range Default Read Write Size