Chapter 8
8-9
Communications Errors
Note Check the Digital Operator display (see the following table) to identify faults when DeviceNet
communications are disabled.
Faults when DeviceNet Communications are Disabled
Inverter Content Countermeasure
3G3MV 3G3RV
3G3PV
3G3FV
F04 CPF04 EEPROM fault
There was an inconsis-
tency in the stored data or
there is a hardware fault.
Store the parameters again
Turn the power supply OFF and then ON again.
Replace the Inverter if the steps above do not elimi-
nate the fault.
Note: This fault may occur if the number of overwrite
operations exceeds 100,000. EEPROM is over-
written when a parameter change operation is
executed from a Parameter Unit or an ENTER
command is sent. Overwrite the data in EEPROM
as little as possible.
--- ERR EEPROM write fault
F06 CPF06 Option Unit/Card self-test
error
Install the DeviceNet Communications Unit/Card cor-
rectly.
Align the case with the connector of the DeviceNet
Communications Unit/Card so that it is fully installed.
F21 CPF21 Option Unit/Card self-test
error
Install the DeviceNet Communications Unit/Card cor-
rectly.
Turn the power supply OFF and then ON again.
Replace the DeviceNet Communications Unit/Card if
the steps above do not eliminate the fault.
F22 CPF22 Option Unit/Card model
code error
Install the DeviceNet Communications Unit/Card cor-
rectly.
Turn the power supply OFF and then ON again.
Replace the DeviceNet Communications Unit/Card if
the steps above do not eliminate the fault.
F23 CPF23 Option Unit/Card mutual
test error
A communications error
occurred between the
DeviceNet Communica-
tions Unit/Card and
Inverter.
Install the DeviceNet Communications Unit/Card cor-
rectly.
Align the case with the connector of the DeviceNet
Communications Unit/Card so that it is fully installed.
Check whether the DeviceNet Communications Unit/
Card’s FG wire is properly connected to the Inverter.
Take steps to reduce noise in the DeviceNet commu-
nications lines. (See 3-3 Communications Line Noise
Prevention for details.)
Replace the DeviceNet Communications Unit/Card if
the steps above do not eliminate the fault.