Chapter 9
9-14
Communications Programs (CS-series PLCs)
Program-related Bits Used
Inverter Control Input
002005 Frequency Detect 2 (1: output frequency
n095) Bit
002006 Inverter Ready (1: Inverter ready) Bit
002007 UV (1: UV) Bit
002008 Baseblock (1: baseblock) Bit
002009 Frequency Reference Mode (1: not communi-
cations) Bit
002010 Run Command Mode (1: not communications)
Bit
002011 Overtorque Detection (1: overtorque detected)
Bit
002012 Not used.
002013 during Fault Retry (1: during fault retry) Bit
002014 Fault (1: during fault) Bit
002015 Communications Timeover CE (1: communica-
tions timeover detected) Bit
Word Function
000000 Program Start Input Bit
000001 Program End Input Bit
000002 Program Execution Flag
000003 Communications Error Reset Input Bit
000004 Inverter Stop Command Flag
000100 Frequency Reference Write Flag
000101 Control Input Write Flag
000102 Output Frequency Read Flag
000103 Inverter Status Read Flag
000300 Frequency Reference Write Completed Flag
000301 Control Input Write Completed Flag
000302 Output Frequency Read Completed Flag
000303 Inverter Status Read Completed Flag
003110 Communications Error Flag
Word Function
D01000 Reference frequency setting
D02000 Output frequency monitor
Word Function