Chapter 10
10-37
Appendices
■ Function Group 2 (n050 to n079)
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
n050 0132 01 32 Multi-function input 1 (terminal S1) 1 to 27 1 1 No
n051 0133 01 33 Multi-function input 2 (terminal S2) 1 to 27 1 2 No
n052 0134 01 34 Multi-function input 3 (terminal S3) 0 to 27 1 3 No
n053 0135 01 35 Multi-function input 4 (terminal S4) 1 to 27 1 5 No
n054 0136 01 36 Multi-function input 5 (terminal S5) 1 to 27 1 6 No
n055 0137 01 37 Multi-function input 6 (terminal S6) 1 to 27 1 7 No
n056 0138 01 38 Multi-function input 7 (terminal S7) 1 to 27,
34, 35
110No
n057 0139 01 39 Multi-function input 1 (MA/MB-MC) 0 to 21 1 0 No
n058 013A 01 3A Multi-function input 2 (P1-PC) 0 to 21 1 1 No
n059 013B 01 3B Multi-function input 3 (P2-PC) 0 to 21 1 2 No
n060 013C 01 3C Frequency reference gain 0 to 255 1% 100 Yes
n061 013D 01 3D Frequency reference bias −100 to
100
1% 0 Yes
n062 013E 01 3E Analog frequency reference filter time
constant
0.00 to
2.00
0.01 s 0.10 Yes
n063 --- --- --- Not used. --- --- --- ---
n064 0140 01 40 Frequency reference loss detection
selection
0, 110No
n065 0141 01 41 Multi-function analog output type selec-
tion
0, 110No
n066 0142 01 42 Multi-function analog output 0 to 6 1 0 No
n067 0143 01 43 Multi-function analog output gain 0.00 to
2.00
0.01 1.00 Yes
n068 0144 01 44 Multi-function analog voltage input gain −255 to
255
1% 100 Yes
n069 0145 01 45 Multi-function analog voltage input bias −100 to
100
1% 0 Yes
n070 0146 01 46 Multi-function analog voltage input filter
constant
0.00 to
2.00
0.01 s 0.10 Yes
n071 0147 01 47 Multi-function analog current input gain −255 to
255
1% 100 Yes
n072 0148 01 48 Multi-function analog current input bias −100 to
100
1% 0 Yes
n073 0149 01 49 Multi-function analog current input fil-
ter constant
0.00 to
2.00
0.01 s 0.10 Yes
n074 014A 01 4A Pulse train frequency reference gain −255 to
255
1% 100 Yes
n075 014B 01 4B Pulse train frequency reference bias −100 to
100
1% 0 Yes
n076 014C 01 4C Pulse train frequency reference input
filter constant
0.00 to
2.00
0.01 s 0.10 Yes
n077 014D 01 4D Multi-function analog input terminal
function selection
0 to 4 1 0 No
n078 014E 01 4E Multi-function analog input terminal
selection
0, 110No
n079 014F 01 4F Multi-function analog input frequency
bias
0 to 50 1% 10 No