Chapter 10
10-48
Appendices
00 61 0061 OPE error
parameter
Monitors U1-34; outputs parameter
00 63 0063 PID input
quantity
Monitors U1-36; 0.01% units (max. frequency =
100%; with sign)
00 64 0064 PID output
quantity
Monitors U1-37; 0.01% units (max. frequency =
100%; with sign)
00 65 0065 PID reference Monitors U1-38; 0.01% units (max. frequency =
100%)
00 66 0066 RS-422A/485
communica-
tions error
Monitors U1-39
Bit 0 CRC error
Bit 1 Invalid data length
Bit 2 Not used.
Bit 3 Parity error
Bit 4 Overrun error
Bit 5 Framing error
Bit 6 Time-out
Bit 7 to
15
Not used.
00 68 0068 Fan operating
time
Monitors U1-40; 1-hr units
00 80 0080 Current fault Monitors U2-01
Code Error
dis-
play
Code Error
dis-
play
Code Error
dis-
play
01 PUF 0E OL4 1C LF
02 UV1 0F RR 1D OH3
03 UV2 10 RH 1E OPR
04 UV3 11 EF3 1F ERR
06 GF 12 EF4 20 OH4
07 OC 13 EF5 22 BUS
08 OV 14 EF6 25 CF
09 OH 15 EF7 27 EF0
0AOH118OS28FBL
0B OL1 19 DEV 29 UL3
0C OL2 1A PGO 2A UL4
0DOL31BPF2BOL7
00 81 0081 Last fault Monitors U2-02 (same codes as U2-01)
00 82 0082 Fault fre-
quency refer-
ence
Monitors U2-03; 0.01-Hz units (units set in o1-03;
with sign)
00 83 0083 Fault output
reference
Monitors U2-04; 0.01-Hz units (units set in o1-03;
with sign)
00 84 0084 Fault output
current
Monitors U2-05; 0.1-A units
00 85 0085 Fault motor
speed
Monitors U2-06; 0.01-Hz units (units set in o1-03;
with sign)
Class 64 Register
number (hex)
Content
Instance Attribute

Table of Contents

Related product manuals