Chapter 10
10-51
Appendices
Parameters for Initialize Mode
Application Parameters
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
A1-00 0100 01 00 Language selection for Digital Operator
display
0 to 6 1 1 Yes
A1-01 0101 01 01 Parameter access level 0 to 2 1 2 Yes
A1-02 0102 01 02 Control method selection 0 to 2 1 0 No
A1-03 0103 01 03 Initialize 0 to 3330 1 0 No
A1-04 0104 01 04 Password 0 to 9999 1 0 No
A1-05 0105 01 05 Password setting 0 to 9999 1 0 No
A2-01
to
A2-32
0106 to
0125
01 06 to
25
User-parameter settings 0180 to
050C
Set the
register
numbers
for b1-01
to o2-11.
1 --- No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
b1-01 0180 01 80 Reference selection 0 to 4 1 1 No
b1-02 0181 01 81 Operation method selection 0 to 3 1 1 No
b1-03 0182 01 82 Stopping method selection 0 to 3 1 0 No
b1-04 0183 01 83 Prohibition of reverse operation 0 to 2
(See
note 6.)
10No
b1-06 0185 01 85 Read sequence input twice 0, 1 1 1 No
b1-07 0186 01 86 Operation selection after switching to
remote mode
0, 110No
b1-08 0187 01 87 Run command selection in program-
ming modes
0, 110No
b2-01 0189 01 89 Zero speed level (DC injection braking
starting frequency)
0.0 to
10.0
0.1 Hz 0.5 No
b2-02 018A 01 8A DC injection braking current 0 to 100 1% 50 No
b2-03 018B 01 8B DC injection braking time at start 0.00 to
10.00
0.01 s 0.00 No
b2-04 018C 01 8C DC Injection braking time at stop 0.00 to
10.00
0.01 s 0.50 No
b3-01 0191 01 91 Speed search selection (current detec-
tion or speed calculation)
0 to 3 1 2 (See
note 1.)
No
b3-02 0192 01 92 Speed search operating current (cur-
rent detection)
0 to 200 1% 120 (See
note 1.)
No
b3-03 0193 01 93 Speed search deceleration time (cur-
rent detection)
0.0 to
10.0
0.1 s 2.0 No
b3-05 0195 01 95 Speed search wait time (current detec-
tion or speed calculation)
0.0 to
20.0
0.1 s 0.2 No
b4-01 01A3 01 A3 Timer function ON-delay time 0.0 to
3000.0
(See
note 5.)
0.1 s 0.0 No