Chapter 1
1-17
Functions and System Configuration
1-5-4 Inverters
The maximum number of Inverters that can be connected to one Network depends on the PLC
model that is used, the remote I/O functions of the Inverter, and whether message communications
are used or not. (Use the message communications function for setting some parameters and for
monitoring the output current.) The differences between models are provided in the following tables.
■ CS1W-DRM21(-V1) or CJ1W-DRM21 DeviceNet (Master) Units
● Communications without Configurator: Fixed Allocations
Communications distances Baud rate Network length Drop line length Total drop line
length
500 Kbps 100 m max. 6 m max. 39 m max.
250 Kbps 250 m max. 6 m max. 78 m max.
125 Kbps 500 m max. 6 m max. 156 m max.
Communications power supply 24 V DC
±1%, supplied externally
(Slave power supply: 11 to 25 V DC)
Recommended power supply: OMRON S82H Series or S82J Series
Maximum number of nodes 64 nodes
Maximum number of Masters Without Configurator:1
With Configurator: 63
Maximum number of Slaves Without Configurator:63
With Configurator: 63
Error control CRC check
Applicable PLC CS Series CJ Series
DeviceNet (Master) Unit CS1W-DRM21(-V1) CJ1W-DRM21
Supported communications Remote I/O and messages
Maximum number of Slaves
per DeviceNet (Master) Unit
63
Item Specifications