Chapter 10
10-53
Appendices
Note 1. When the control mode is changed, the Inverter will revert to default settings. (The V/F con-
trol default setting is given above.)
Note 2. The default setting is 0.1 for V/f control with PG.
Note 3. The default setting is 2.00 s for Inverters with a capacity of 55 kW or more.
Note 4. The same capacity as the Inverter can be set by initializing this parameter.
Note 5. The setting range for Asian models is 0 to 300.0
Note 6. The setting range for Asian models is 0 to 1.
Tuning Parameters
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
C1-01 0200 02 00 Acceleration time 1 0.0 to
6000.0
(Set with
C1-10.)
0.1 s
(Set with
C1-10.)
10.0 Yes
C1-02 0201 02 01 Deceleration time 1 Yes
C1-03 0202 02 02 Acceleration time 2 Yes
C1-04 0203 02 03 Deceleration time 2 Yes
C1-05 0204 02 04 Acceleration time 3 No
C1-06 0205 02 05 Deceleration time 3 No
C1-07 0206 02 06 Acceleration time 4 No
C1-08 0207 02 07 Deceleration time 4 No
C1-09 0208 02 08 Deceleration Stop Time No
C1-10 0209 02 09 Accel/decel time setting unit 0, 1 1 1 No
C1-11 020A 02 0A Accel/decel time switching frequency 0.0 to
400.0
0.1 Hz 0.0 No
C2-01 020B 02 0B S-curve characteristic time at accelera-
tion start
0.00 to
2.50
0.01 s 0.20 No
C2-02 020C 02 0C S-curve characteristic time at accelera-
tion end
0.00 to
2.50
0.01 s 0.20 No
C2-03 020D 02 0D S-curve characteristic time at decelera-
tion start
0.00 to
2.50
0.01 s 0.20 No
C2-04 020E 02 0E S-curve characteristic time at decelera-
tion end
0.00 to
2.50
0.01 s 0.00 No
C3-01 020F 02 0F Slip compensation gain 0.0 to 2.5 0.1 0.0 (See
note 1.)
Ye s
C3-02 0210 02 10 Slip compensation primary delay time 0 to
10000
1 ms 2000
(See
note 1.)
No
C3-03 0211 02 11 Slip compensation limit 0 to 250 1% 200 No
C3-04 0212 02 12 Slip compensation selection during
regeneration
0, 110No
C3-05 0213 02 13 Output voltage limit operation selection 0, 1 1 0 No
C4-01 0215 02 15 Torque compensation gain 0.00 to
2.50
0.01 1.00 Yes
C4-02 0216 02 16 Torque compensation primary delay
time constant
0 to
10000
1 ms 200 (See
note 1.)
No
C4-03 0217 02 17 Starting torque value (forward) (See
note 4.)
0.0 to
200.0
0.1% 0.0 No
C4-04 0218 02 18 Starting torque value (reverse) (See
note 4.)
200.0 to
0.0
0.1% 0.0 No
C4-05 0219 02 19 Starting torque time constant (See note
4.)
0 to 200 1 ms 10 No