Chapter 10
10-56
Appendices
■ Motor Constant Parameters
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
E1-01 0300 03 00 Input voltage setting 155 to
255 (155
to 510)
(See
note 1.)
1 V 200
(400)
(See
note 1.)
No
E1-03 0302 03 02 V/f pattern selection 0 to F 1 F No
E1-04 0303 03 03 Max. output frequency 40.0 to
400.0
(See
note 5.)
0.1 Hz 50.0
(60.0)
(See
notes 3
and 8.)
No
E1-05 0304 03 04 Max. voltage 0.0 to
255.0
(0.0 to
510.0)
(See
note 1.)
0.1 V 200.0
(400.0)
(See
note 1.)
No
E1-06 0305 03 05 Base frequency 0.0 to
400.0
0.1 Hz 50.0
(60.0)
(See
notes 3
and 8.)
No
E1-07 0306 03 06 Mid. output frequency 0.0 to
400.0
0.1 Hz 3.0 (See
note 3.)
No
E1-08 0307 03 07 Mid. output frequency voltage 0.0 to
255.0
(0.0 to
510.0)
(See
note 1.)
0.1 V 15.0
(30.0)
(See
notes 1
and 3.)
No
E1-09 0308 03 08 Min. output frequency 0.0 to
400.0
0.1 Hz 1.5 (See
note 3.)
No
E1-10 0309 03 09 Min. output frequency voltage 0.0 to
255.0
(0.0 to
510.0)
(See
note 1.)
0.1 V 9.0
(18.0)
(See
notes 1
and 3.)
No
E1-11 030A 03 0A Mid. output frequency 2 0.0 to
400.0
0.1 Hz 0.0 (See
note 6.)
No
E1-12 030B 03 0B Mid. output frequency voltage 2 0.0 to
255.0
(0.0 to
510.0)
(See
note 1.)
0.1 V 0.0 (See
note 6.)
No
E1-13 030C 03 0C Base voltage 0.0 to
255.0
(0.0 to
510.0)
(See
note 1.)
0.1 V 0.0 (See
note 4.)
No
E2-01 030E 03 0E Motor rated current 0.32 to
6.40
(See
note 2.)
0.01 A Depends
on
capacity.
No
E2-02 030F 03 0F Motor rated slip 0.00 to
20.00
0.01 Hz Depends
on
capacity.
No