Chapter 10
10-64
Appendices
Note 1. Values in parentheses are for Asian model Inverters.
Note 2. Set T1-02 and T1-04 when T1-01 is set to 2. This setting (2) is only possible for V/f control
or V/f control with PG.
■ Motor Autotuning Parameters
Note 1. Values in parentheses are for 400-V-class Inverters.
Note 2. Set T1-02 and T1-04 when T1-01 is set to 2. This setting (2) is only possible for V/f control
or V/f control with PG.
o2-03 0507 05 07 Parameter initial value 0 to 2 1 0 No
o2-04 0508 05 08 kVA selection 0 to FF 1 Depends
on
capacity.
No
o2-05 0509 05 09 Frequency reference setting method
selection
0, 110No
o2-06 050A 05 0A Operation selection when digital opera-
tor is disconnected
0, 110No
o2-07 050B 05 0B Cumulative operation time setting 0 to
65535
1 hr 0 No
o2-08 050C 05 0C Cumulative operation time selection 0, 1 1 1 (0)
(See
note 1.)
No
o2-09 050D 05 0D Initialize mode Do not change. --- --- --- No
o2-10 050E 05 0E Fan operation time setting 0 to
65535
1 hr 0 No
o2-11 0510 05 10 Fault trace/fault history initialization
(See note 2.)
0, 110No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
T1-00 0700 07 00 Motor 1/2 selection 1, 2 1 1 No
T1-01 0701 07 01 Autotuning mode selection 0 to 2
(See
note 2.)
10No
T1-02 0702 07 02 Motor output power 0.00 to
650.00
0.01 kW 0.40 No
T1-03 0703 07 03 Motor rated voltage 0.0 to
255.0
(0.0 to
510.0)
(See
note 1.)
0.1 V 200.0
(400.0)
(See
note 1.)
No
T1-04 0704 07 04 Motor rated current 0.32 to
6.40
(See
note 3.)
0.01 A Depends
on
capacity.
No
T1-05 0705 07 05 Motor base frequency 0.00 to
400.00
(See
note 4.)
0.01 Hz 60.00 No
T1-06 0706 07 06 Number of motor poles 2 to 48 1 4 No
T1-07 0707 07 07 Motor base speed 0 to
24000
1 r/min 1750 No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute