Chapter 10
10-70
Appendices
00 4B 004B Operating
status
Monitors U1-12
Bit 0 During RUN
Bit 1 Zero speed
Bit 2 Forward/reverse (1: Reverse operation)
Bit 3 During fault reset input
Bit 4 Frequency agree
Bit 5 Operation ready
Bit 6 Alarm (minor fault)
Bit 7 Fault
Bits 8 to
F
Not used.
00 4C 004C Cumulative
operation
time
Monitors U1-13; 1-hr units
00 4D 004D FLASH ID
software No.
Monitors U1-14
00 4E 004E Frequency
reference
(voltage):
Ter mi n a l A 1
input value
Monitors U1-15; 0.1% units (100% = 10 V; with sign for +
voltage setting)
00 4F 004F Multi-func-
tion analog
input: Termi-
nal A2 input
value
Monitors U1-16; 0.1% units (100%=20 mA or 100% = 10 V;
with sign for
± voltage setting)
--- --- 0051 and
0052
Not used.
00 53 0053 Output fre-
quency after
a soft start
Monitors U1-20; 0.01-Hz units (with sign)
--- --- 0054 and
0055
Not used.
00 57 0057 PID feed-
back
Monitors U1-24; 0.01% units (input corresponding to max.
frequency = 100%; with sign)
--- --- 0059 and
005A
Not used.
00 5B 005B CPU ID Monitors U1-28
--- --- 005F and
0060
Not used.
00 61 0061 OPE error
parameter
Monitors U1-34; outputs parameter
00 63 0063 PID input
quantity
Monitors U1-36; 0.01% units (max. frequency = 100%; with
sign)
00 64 0064 PID output
quantity
Monitors U1-37; 0.01% units (max. frequency = 100%; with
sign)
00 65 0065 PID refer-
ence
Monitors U1-38; 0.01% units (max. frequency = 100%)
Class 64 Register No.
(Hex)
Contents
In-
stance
At-
tribute