Chapter 3
3-26
Setup and Wiring
3G3MV-PDRT2 DeviceNet Communications Unit
Mount the Unit in a metal control panel, as shown in the diagram. Detailed precautions are given
below.
Remove any coating on the footprints of EMC filter, Inverter, and metal mounting plate in order to
ensure a metal contact between grounding faces.
Mount the inverter on top of an EMC-compliant input noise filter and attach any Option Units.
Use a shielded cable for the Inverter power supply line and connect via the EMC-compliant input
noise filter with the shortest cable length possible. Ground the shield at both ends of the cable.
L1L2
Control Panel
Metal Mounting
Plate
IM
3
L3
R S T U V W
L1 L2 L3
E
E
PE
3G3MV-PDRT
SYSDRIVE
3
G
3
M
V
I
N
V
E
R
T
E
R
RUN
ALARM
EMC-compliant
input noise
filter
3G3MV
Inverter
ZCAT3035-1330
Clamp Filter
(manufactured
by TDK)
AC power
supply
PLC with DeviceNet master
Motor
3-phase
noise filter
Grounding
faces
MV-series
Inverter
Grounding faces
Shielded
cable
Motor cable
(20 m max.)
Wiring Diagram for Inverter