EasyManua.ls Logo

Omron 3G3MV-PDRT2 - Devicenet Communications Settings

Omron 3G3MV-PDRT2
363 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4
4-8
SYSDRIVE Inverter Settings
4-2-3 DeviceNet Communications Settings
The parameters below are for functions that are exclusive to DeviceNet communications. Set these
parameters according to the desired application.
Note If F6-01 is set to 3 (continues operating), the Inverter will continue operating when a communi-
cations fault occurs according to the contents of settings immediately before. Be sure to take
any steps necessary to ensure safety, such as installing a limit switch or an emergency stop
switch.
Parameter
No.
Name Contents Setting
range
Default
setting
Operator display
F6-01 Communications fault opera-
tion
Select the Inverter operation per-
formed when a communications
fault is detected.
0: Decelerates to a stop using C1-
02 deceleration time/fault detec-
tion
1: Coasts to a stop/fault detection
2: Decelerates to a stop using the
C1-09 emergency stop time/
fault detection
3: Continues operating/alarm
detection (See note.)
0 to 3 1
Comm Bus Flt Sel
F6-02 Communications external fault
input: detection method
Select the detection method used
for the communications external
fault input from communications
(DeviceNet Communications
Card).
0: Faults always detected.
1: Faults detected only while run-
ning (i.e., when Run Com-
mands are input)
0, 1 0
EFO Detection
F6-03 Communications external fault
input: operation
Select the Inverter operation per-
formed when there is a communi-
cations external fault (EFO) input
from communications (DeviceNet
Communications Card).
0: Decelerates to a stop using C1-
02 deceleration time/fault detec-
tion
1: Coats to a stop/fault detection
2: Decelerates to a stop using the
C1-09 emergency stop time/
fault detection
3: Continues operating/alarm
detection
0 to 3 1
EFO Fault Action
F6-04 Not used Do not set. --- 0
Trace Sample Tim

Table of Contents

Related product manuals