EasyManua.ls Logo

Omron ACCURAX G5 - Page 496

Omron ACCURAX G5
553 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11-10
11-3 Alarm List
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
11
Error and Maintenance
Extended Alarms
Error No.
Error detection function Detection details and probable cause
Main Sub
46 0 Absolute Error Absolute encoder status is abnormal
51 6 External Scale Error External scale status is abnormal
70
0
U-Phase Phase Current
Detection Error
U-Phase Current Detection Value is abnormal when
objecting servo off to servo on
1
W-Phase Phase Current
Detection Error
W-Phase Current Detection Value is abnormal when
objecting servo off to servo on
2
Current Detection Syste
Error
Setting value of Current Detection Systemu is abnormal
71
0 AI2 Input Error
Analog Input Voltage 2 value is abnormal +11 V over is
lasting 200 ms
1 AI3Input Error
Analog Input Voltage 3 value is abnormal +11 V over is
lasting 200 ms
72 0 Thermal Error Hardware is abnormal
73 0
VDC Detection System
Error
Hardware is abnormal
76
0 Internal RAM Error Microcomputer is abnormal
1 Internal ROM Error Internal ROM is abnormal
77 0 Stacke Error Lack of Stack Area
78 0 Encoder EEPROM Error Encoder EEPROM Check is abnormal
96 0 LSI Initialization Error Falut of MNM1223 initialization
97 0 Setting Error Encoder type and control mode are unmatching
99 0 Hardware Error Power curcuit detects the something hardware error
99 1 Encoder Setting Error Encoder Setting is not correct

Table of Contents