12-2 Parameter List
Accurax G5 AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
12
Appendix
Note 1: Pn003 default settings:
(1) Pn003 = 11 - For 200V drives of 1Kw or upper and 400V drives
(2) Pn003 = 13 - For 200V drives of less than 1 Kw
Note 2: Pn016 default settings:
(1) Pn016 = 0 - For 200V drives of 750 W or upper and 400V drives
(2) Pn016 = 3 - For 200V drives of less than 750 W
Gain Adjustment Parameters
016
Regeneration
Resistor
Selection
Select the Regeneration Resistor used.
See
Note 2
− 0 to 3 Yes
0
Use the Built-in Resistor.
Triggering of regeneration overload
protection (alarm display No. 18)
depends on the Built-in Resistor (with
approx. 1% duty).
1
Use an External Resistor.
The regeneration processing circuit
operates and regeneration overload
protection (alarm display No. 18) is
triggered when the operating rate of the
Regeneration Resistor exceeds 10%.
2
Use an External Resistor.
Regeneration overload protection
(alarm display No. 18) does not operate.
3
No Regeneration Resistor
All regeneration power is processed
with built-in capacitors.
017
External
Regeneration
Resistor Setting
Select the type of load ratio calculation for
the External Regeneration Resistor.
0 − 0 to 4 Yes
0
Regeneration load ratio is 100% when
operating rate of the External
Regeneration Resistor is 10%.
1Reserved
2Reserved
3Reserved
4Reserved
Pn number
Parameter
name
Explanation
Default
setting
Unit
Setting
range
Power
supply
OFF to
ON