Remote Terminals
G72C-ID16 (Input)
Rated input voltage 24 VDC 12 VDC
Rated input current 9.7 mA/point 10.9 mA/point
ON voltage 15 VDC min. 8 VDC min.
OFF voltage 5.6 VDC max. 3.5 VDC max.
ON response time 1.5 ms max.
OFF response time 1.5 ms max.
Number of circuits 16 points/common
Insulation method Photocoupler insulation
Input indicator LED indicator (green)
RUN output G6B 1a contact relay (closed during operation)
Contact capacity: 2 A max. at 250 VAC or 24 VDC (cos
φ =1)
Diagnostic functions Transmission error checks
BCC and reversed transmission verification
CPU Unit error monitoring
Power consumption 200 mA max. 300 mA max.
Weight 400 g max.
G72C-OD16 (Output)
Rated output voltage 24 VDC 12 VDC
Rated output current 0.3A/point, 2.4 A/Unit
Residual voltage 1.2 V max.
Leakage current
100
µA max.
Number of circuits 16 points/common
Insulation method Photocoupler insulation
Output indicator LED indicator (green)
RUN Output G6G 1a contact relay (closed during operation) Contact capacity: 2A max. at
250 VAC or 24 VDC (cos
φ =1)
Diagnostic functions Transmission error checks (BCC and reversed transmission verification)
CPU Unit error monitoring
Power consumption 200 mA max. 300 mA max.
Weight 400 g max.