566
Specifications of Basic I/O Units Appendix A
Terminal Connections
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
CJ1W-OC211 Contact Output Unit (Terminal Block, 16 Points)
0
1
2
3
4
5
6
7
C0
C1
C2
C3
C4
C5
C6
C7
2 A 250 V AC,
2 A 24 V DC max.
Polarity of the DC
power supply can be
connected in either
direction because
relay contacts are
used.
Max. Switching Capacity 2 A 250 V AC (cosφ = 1), 2 A 250 V AC (cosφ =
0.4), 2 A 24 V DC (8 A/Unit)
Min. Switching Capacity 1 mA 5 V DC
Service Life of Relay Electrical: 150,000 operations (24 V DC, resistive
load)/ 100,000 operations (250 V AC, cosφ = 0.4,
inductive load)
Mechanical: 20,000,000 operations
Service life will vary depending on the connected
load. Refer to page 586 for information on service
life according to the load.
Relay replacement NY-24W-K-IE (Fujitsu Takamizawa Component
Ltd.)
Relays cannot be replaced by users.
ON Response Time 15 ms max.
OFF Response Time 15 ms max.
Number of Circuits 16 points/common, 1 circuit
Insulation Resistance 20 MΩ between external terminals and the GR
terminal (500 V DC)
Dielectric Strength 2,000 V AC between the external terminals and
the GR terminal for 1 minute at a leakage current
of 10 mA max.
Internal Current Consumption 110 mA 5 V DC max. 96 mA 24 V DC (6 mA × No.
points ON)
Weight 170 g max.