Specifications of Basic I/O Units Appendix A
Circuit Configuration
Terminal Connections
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
CJ1W-OA201 Triac Output Unit (8 Points)
Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used
for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O
tables.
Output indicator
Internal circuits
to
2 A 250 V AC,
2 A 24 V DC max.
Max. Switching Capacity 0.6 A 250 V AC, 50/60 Hz (2.4 A/Unit)
Max. Inrush Current 15 A (pulse width: 10 ms)
Min. Switching Capacity 50 mA 75 V AC
Leakage Current 1.5 mA (200 V AC) max.,
Residual Voltage 1.6 V AC max.
ON Response Time 1 ms max.
OFF Response Time 1/2 of load frequency+1 ms or less.
Number of Circuits 8 (8 points/common)
Surge Protector C.R Absorber + Surge Absorber
Fuses 5 A (1/common, 1 used)
The fuse cannot be replaced by the user.
Insulation Resistance 20 MΩ between the external terminals and the GR
terminal (500 V DC)
Dielectric Strength 2,000 V AC between the external terminals and
the GR terminal for 1 minute at a leakage current
of 10 mA max.
Internal Current Consumption 220 mA max.
Weight 150 g max.