568
Specifications of Basic I/O Units Appendix A
Circuit Configuration
Terminal Connections
CJ1W-OD201 Transistor Output Unit (Terminal Block, 8 Points, Sinking)
Note Although 16 I/O bits (1 word) are allocated, only 8 of these can be used
for external I/O. This Unit is also treated as a 16-point I/O Unit in the I/O
tables.
COM
OUT
OUT7
to
Internal circuits
Output indicator
Fuse
0
1
2
3
5
6
7
4
COM
L
NC
NC
NC
NC
NC
NC
NC
NC
NC
L
L
L
L
L
L
L
A0
A1
A2
A3
A4
A5
A6
A7
A8
B8
B7
B6
B5
B4
B3
B2
B1
B0
250 V AC max.
Rated Voltage 12 to 24 V DC
Operating Load Voltage Range 10.2 to 26.4 V DC
Maximum Load Current 2.0 A/point, 8.0 A/Unit
Maximum Inrush Current 10 A/point, 10 ms max.
Leakage Current 0.1 mA max.
Residual Voltage 1.5 V max.
ON Response Time 0.5 ms max.
OFF Response Time 1.0 ms max.
Insulation Resistance 20 MΩ between the external terminals and the GR
terminal (100 V DC)
Dielectric Strength 1,000 V AC between the external terminals and the
GR terminal for 1 minute at a leakage current of
10 mA max.
Number of Circuits 8 (4 points/common, 2 circuits)
Internal Current Consumption 5 V DC: 90 mA max.
Fuse 6.3 A (1/common, 2 used)
The fuse cannot be replaced by the user.
External Power Supply 12 to 24 V DC, 10 mA min.
Weight 110 g max.