204
Refer to the following table to set signed binary data to use the monitor output
function.
Set output binary data Output voltage (V)
2710 (10000) min. 9.999
270F (9999) 9.999
0000 0000
D8F1 (–9999) –9.999
D8F0 (–10000) max. –9.999
There is no setting range restriction except for the following cases.
If the signed binary data of the CQM1-LSE02 output word is the same as or less
than D8F0 (–10000), –9.999 V will be output from the monitor output terminal. If
the signed binary data of the CQM1-LSE02 output word is the same as or larger
than 2710 (10000), 9.999 V will be output from the monitor output terminal.
Note When obtaining the value to be set to the output word through calculation using
the ladder program, be careful not to use the computed result of “C000 to CFFF.”
Even when the Unit is used in the set data D/A output mode, if “C000 to CFFF” is
set to the output word, it is treated as a command.
In this mode, analog input is converted into digital data and then converted into
analog output. Therefore, the obtained analog output is not highly precise.
Monitor Output
Section 6-5