207
Set Commands Operation Mode A Set
Operation Mode B Set
Scaling Value Set
Set Value Set
Hysteresis Set
Output word
Input word
Command
Command code
(1)
(2)
(3)
Parameter
Response
Command code Parameter
(4)
(5)
1, 2, 3... 1. Set the command code to the output word. The Unit will check the command
code. If the command code is correct, the same command code will be set to
the input word as the response for the command. If the command code is
incorrect, an error code will be set to the input word.
2. After confirming that the response sent back to the input word is correct, set
a parameter to the output word.
3. The Unit will check the parameter. If the parameter is correct, the parameter
will be set to the input word as the response for the parameter. If the parame-
ter is incorrect, an error code will be set to the input word.
4. After confirming that the response sent back to the input word is correct, set
0000 to the output word. The scaled conversion data or comparison result
will stored in the input word.
Scaling Value Read
Set Value Read
Hysteresis Read
Sign of
set value
(1)
(2)
(3)
Set value
Sign of
set value
Set value
Output word
Input word
Command
Command code
Response
(2)
1, 2, 3... 1. Set the command code to the output word. The Unit will check the command
code. If the command code is correct, the sign for a set value will be set to the
input word corresponding to the command as the response for the com-
mand. If the command code is incorrect, an error code will be set to the input
word.
The set value will be set to the input word approximately 0.5 s after the sign is
set to the input word. The sign and set value will be set to the input word al-
ternately at approximately 0.5-s intervals.
2. After confirming that the sign and the set value that the input word is set to is
correct, set 0000 to the output word.
3. The scaled conversion data or comparison result will stored in the input
word.
Signed Set Value Read
Commands
Command Usage Section 7-1