Units for Platinum Resistance Thermometers
Loop 2
Loop 4
Output 2
Output 4
+24 VDC
(from external
power supply)
Output 1
Output 3
Loop 3
Loop 1
CQM1-TC301
(4 loops, NPN
outputs)
CQM1-TC302
(4 loops, PNP
outputs)
CQM1-TC303
(2 loops, heater burnout
alarm NPN outputs)
CQM1-TC304
(2 loops, heater burnout
alarm PNP outputs)
Output 2
Output 4
+24 VDC
(from external
power supply)
Output 1
Output 3
Loop 3
Loop 1
Loop 2
Loop 4
Output 2
+24 VDC
(from external
power supply)
Output 1
Loop 1
Loop 2
Output 2
+24 VDC
(from external
power supply)
Output 1
Loop 1
Loop 2
• The +DC terminals for NPN outputs are internally connected.
• The 0V terminals for NPN outputs are internally connected.
Use M3 crimp connectors and tighten terminal screws to a torque of 0.3 to
0.5 Nm
6.2 mm max. 6.2 mm max.
Control output
Heater
AC power
Connect to CT input
terminals on the
Temperature Control
Unit (no polarity).
Heater wire
Current Detector
(E54-CT1/CT3)
CT
Output Interface
Maximum switching capability 100 mA, 24 VDC
+10%
/
–15%
Leakage current 0.1 mA max.
Residual voltage 0.8 V max.
External supply voltage 30 mA min., 24 VDC
+10%
/
–15%
(excluding load current)
When the short-circuit protection circuit operates, turn OFF the output or the out-
put power supply, or release the short circuit.
Crimp Terminals
Current Detectors
(E54-CT1/CT3)
Output Characteristics
Built-in Short-circuit
Protection Circuit
Wiring