15
2-2 Switch Settings
Remove the terminal block to expose the DIP switch underneath. Refer to the
CQM1H Operation Manual (W363) or the CQM1 Operation Manual (W226) for
the method of removing the terminal block.
Use a thin-tipped object, such as a small screwdriver, to set the pins.
DIP switch
CQM1-B7A21/CQM1-B7A12
Pin no. Setting OFF ON
4 Transmission delay
time
STANDARD (19.2 ms) RAPID (3 ms)
3 Transmission error
processing
HOLD LOAD OFF
2 Input mode 16IN 15IN+ERR
1 ERR indicator Not lit Lit
Note On delivery from the factory, pin 1 is set ON and all others OFF.
CQM1-B7A03/CQM1-B7A02
Pin no. Setting OFF ON
4 Transmission delay
time
STANDARD (19.2 ms) RAPID (3 ms)
3 Not used (set OFF) ––– –––
2 Not used (set OFF) ––– –––
1 Not used (set OFF) ––– –––
Note On delivery from the factory, all pins set OFF.
CQM1-B7A13
Pin no. Setting OFF ON
6 Transmission delay
time
STANDARD (19.2 ms) RAPID (3 ms)
5 Transmission error
processing
HOLD LOAD OFF
4 Input mode 16IN 15IN+ERR
3 ERR1 indicator Not lit Lit
2 ERR2 indicator Not lit Lit
1 Not used (set OFF) ––– –––
Note On delivery from the factory, pins 2 and 3 are set ON and all others OFF.
Caution Turn off the CQM1H/CQM1 power before setting the pins.