30
Configuration as a Single System with Expansion Masters
Master (32 input points/32 output points max.)
Expansion Master Unit 1 (max. 32 input points or 32 output points)
Expansion Master Unit 2 (max. 32 input points or 32 output points)
RS-485, 200 m max.
G730-VI (input model) G730-VO (output model) G730-RI (input model) G730-RO (output model)
Switch Sensor Lamp ValveSwitch
CQM1H/CQM1
Note 1. Use one Master in any system. The systems must be separated if multiple
Masters are used. (See page 31)
2. Up to two Expansion Masters can be connected to each Master.
3. When two Expansion Masters are used, set one as Unit 1 and the other as
Unit 2. The Slave address for Unit 2 can only be used for an 8-point or
16-point Slave. It cannot be used for a 4-point Slave.
4. The combination of one Master with two Expansion Masters allows control
of up to 128 points.
5. The maximum number of connectable Slaves is 24 4-point Slaves and 4
8-point Slaves, making a total or 28 Units.
System Configuration
Section 1-2