8-7
8 Message Communications
NJ-series CPU Unit Built-in EtherNet/IP Port Users Manual (W506)
8-2 Using CIP Message Communications
8
8-2-4 Route Path
The notation of the route path is different for communications on the built-in EtherNet/IP port and for
communication on an EtherNet/IP Unit. This section provides examples of route paths.
z Communicating between Built-in EtherNet/IP Ports
Example: Communicating between Built-in EtherNet/IP Ports on CPU Unit 1 and CPU Unit 2
Network type number: #02” (Output the command via EtherNet/IP port.)
Remote address: Specify the remote IP address.
Route path: \02\192.168.250.2
z Communicating from a Built-in EtherNet/IP Port to an EtherNet/IP Unit
Example: Communicating from the built-in EtherNet/IP port on CPU Unit 1 to CPU Unit 2 via the Eth-
erNet/IP Unit mounted to CPU Unit 2
(1) CPU Unit 1 to EtherNet/IP Unit 2
Network type number: #02 (Output the command via EtherNet/IP port.)
Remote address: Specify the remote IP address.
(2) EtherNet/IP Unit 2 to CPU Unit 2
Network type number: #01” (Output the command via internal backplane port.)
Remote address: #00” (unit address of CPU Unit)
Route Path Notation Examples
Built-in EtherNet/IP
port
IP address:
192.168.250.2
CPU Unit 2
Built-in EtherNet/IP port
Communications
port (#02)
CPU Unit 1
Backplane
port #01
EtherNet/IP port
IP address:
192.168.250.2
EtherNet/IP Unit 2
Unit address
00 hex
CPU Unit 2
Built-in EtherNet/IP port
Communications
port (#02)
CPU Unit 1
\02\192.168.250.2\01\#00
(2) Unit address of remote CPU Unit
(1) IP address of remote EtherNet/IP Unit
Route path
(1) (2)
: