8-31
8 Message Communications
NJ-series CPU Unit Built-in EtherNet/IP Port Users Manual (W506)
8-3 CIP Objects Sent to the Built-in EtherNet/IP Port
8
8-3-2 Identity Object (Class ID: 01 Hex)
(1) Status Details of the Built-in EtherNet/IP Port
06 hex Serial Number Serial number Read UINT Set value
07 hex Product Name Product name Read STRING Set value
Bit Name Description
0 Owned Indicates when the built-in EtherNet/IP port has an open connection as the
target of a tag data link.
1 Reserved Always FALSE.
2 Configured Tag data link settings exist.
3 Reserved Always FALSE.
4 to 7 Extended Device Status Indicates the status of the built-in EtherNet/IP port.
8 Minor Recoverable Fault TRUE when any of the following errors occurs.
TCP/IP Advanced Setting Error
DNS Server Connection Error
Tag Data Link Setting Error
Tag Data Link Error
Tag Data Link Connection Failed
FTP Server Settings Error
NTP Client Setting Error
SNMP Settings Error
NTP Server Connection Error
Tag Resolution Error
9 Minor Unrecoverable Fault TRUE when the following error occurs.
Identity Error
10 Major Recoverable Fault TRUE when any of the following errors occurs.
IP Address Duplication Error
BOOTP Server Error
Basic Ethernet Setting Error
TCP/IP Basic Setting Error
11 Major Unrecoverable Fault TRUE when any of the following errors occurs.
Communications Controller Error
MAC Address Error
12 to 15 Reserved Always FALSE.
Attribute ID Parameter name Description Attribute
Read data
Data
type
Value
b7 b6 b5 b4
0 1 0 1 There is a major fault.
0 0 1 0 A timeout occurred in one or more target con-
nections.
0 0 1 1 Indicates that there are no tag data link settings.
0 1 1 0 Indicates that one or more connections are per-
forming communications normally.
0 1 1 1 Other than the above.