14 Troubleshooting
NJ-series CPU Unit Built-in EtherNet/IP Port Users Manual (W506)
14-2 Troubleshooting
14
14-2-2 Error Descriptions
Error Descriptions
Event name User Program/Controller Configurations and Setup Trans-
fer Error
Event code 10200000 hex
Meaning The user program or Controller Configurations and Setup were not transferred correctly.
Source PLC Function Module
Motion Control Function Module
EtherCAT Master Function Module
EtherNet/IP Function Module
Source details None Detection
timing
At power ON or
Controller reset
Error attributes Level Major fault Recovery Cycle the power
supply or reset
the Controller.
Log category System
Effects User program Stops. Operation All outputs are stopped.
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
The user program or Controller Con-
figurations and Setup are not correct
because the power supply to the Con-
troller was interrupted or communica-
tions with the Sysmac Studio were
disconnected during a download of
the user program or the Controller
Configurations and Setup.
Clear all of memory and then down-
load the project from the Sysmac Stu-
dio. If attached information is
registered, cycle the power supply to
the Controller and then implement the
above correction.
Do not turn OFF the power supply to
the Controller or disconnect commu-
nications with the Sysmac Studio dur-
ing a download of the user program or
the Controller Configurations and
Setup.
The user program or Controller Con-
figurations and Setup are not correct
because the power supply to the Con-
troller was interrupted during online
editing.
Do not interrupt the power supply to
the Controller during online editing.
The user program or Controller Con-
figurations and Setup are not correct
because the power supply to the Con-
troller was interrupted during a Clear
All Memory operation.
Do not interrupt the power supply to
the Controller during a Clear All Mem-
ory operation.
Non-volatile memory failed. If the error persists even after you
make the above correction, replace
the CPU Unit.
None
Attached
information
Attached Information 1: Cause Details
None: Power was interrupted or communications were disconnected during a download or power was interrupted dur-
ing online editing.
Downloading/Predownloading: For other causes, the timing of error occurrence (during download or during download
preparations) is given.
Precautions/
Remarks
None