14 Troubleshooting
14-24
NJ-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Event name NTP Client Setting Error Event code 34250000 hex
Meaning An error was detected in the NTP client settings.
Source EtherNet/IP Function Module Source details NTP Detection
timing
At power ON or
Controller reset
Error attributes Level Minor fault Recovery Automatic recov-
ery (after down-
loading the NTP
settings), cycle
the power sup-
ply, or reset Con-
troller
Log category System
Effects User program Continues. Operation NTP operation stops.
Indicators EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
--- Flashes at 1-s intervals. ---
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
Power was interrupted when a down-
load was in progress for the NTP cli-
ent settings.
Cycle the power supply to the Con-
troller or reset the Controller. If normal
operation is restored by cycling the
power supply to the Controller or
resetting the Controller, a memory
error has occurred and may occur
again. Replace the CPU Unit. If oper-
ation is not restored even after you
cycle the power supply or reset the
Controller, perform either of the fol-
lowing operations and download the
settings again.
• Memory All Clear operation.
• Identify the cause of error from
those listed in the event log details
and correct the settings.
If operation is not recovered by the
above, replace the CPU Unit.
Do not turn OFF the power supply to
the Controller while a download is in
progress for the NTP client settings.
Memory error None
Attached
information
Attached information 1: Type of errors (01 hex: Non-volatile memory access error, 02 hex: Inconsistency in settings)
Precautions/
Remarks
The cause of error can be identified with the attached information.