2-3 Countermeasures Against Position Deviation
Origin Search Position Deviates
There are some reasons for position deviation after origin search completion.
Position deviation will occur whenever the origin is searched if any coupling or joint of the machine system
has a problem.
If the position between the origin proximity sensor and that of the encoder’s Z phase are too close to each
other, there will be a deviation of one rotation of the motor (1/2 rotation if the M Series is used).
Probable cause Item to check Countermeasure
A joint of the machine system
deviates.
A joint of the machine system
(especially a section where parts
are connected with friction) devi-
ates.
*Such a section can be easily found
by marking it.
Increase the joint strength.
The position of the origin proximity
sensor and that of the encoder’s Z
phase are too close to each other.
There is a deviation of one rota-
tion of the motor (or 1/2 rotation
if the M Series is used) on
completion of origin search.
*Cause of Origin Deviation
Origin proximity sensor
Sensor deflection
Motor’s Z phase
Due to the deflection of the origin
proximity sensor, it will be un-
known whether the machine origin
will be a or b.
If the sensor is a proximity sensor,
the origin varies with the sensing
distance and ambient temperature.
Move the position of the origin
proximity sensor for a distance
of 1/2 rotation of the motor (or
1/4 rotation if the M Series is
used).
Loosen the coupling that con-
nects the motor shaft and the
machine system, turn the motor
shaft for 1/2 rotation of the motor
(or 1/4 rotation if the M Series is
used), and tighten the coupling
again.
The Position Control Unit Stops Abruptly.
Position Deviation with Insufficient Moving Distance Occurs.
The Position Control Unit in positioning operation stops abruptly and then starts operating again.
The Position Control Unit abruptly decelerates to a stop with heavy shock being imposed on the machine
system.
Probable cause Item to check Countermeasure
The incorrect deviation counter
reset or origin reset signal is input.
The incorrect deviation counter
reset or origin reset signal is in-
put in the program.
Correct the program.
Noise is affecting the deviation
counter reset or origin reset
command signal line.
Take countermeasures against
noise. Refer to Chapter 4 Coun-
termeasures Against Noise.
Connection to Position Control Unit Chapter 2