G5-series AC Servomotors and Servo Drives User’s Manual (with Built-in EtherCAT Communications)
A-3 Sysmac Error Status Codes
App
A-3-2 Error Description
Event name Regeneration Overload Event code 34E30000 hex
Meaning The regenerative energy exceeds the processing capacity of the Regeneration Resistor.
Source EtherCAT Master Function Module Source details Slave Detection
timing
While power is
supplied to motor
Error attributes Level Minor fault Recovery Error reset (after
cycling slave
power)
Log category System
Effects User program Continues. Operation Power drive circuit is OFF for relevant slave.
Indicators EtherCAT NET RUN EtherCAT NET ERR EtherCAT LINK/ACT
--- --- ---
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Remedy Prevention
The load inertia is too large. Or, the
Servomotor rotation speed is too high
to absorb the regenerative energy
within the specified deceleration time.
Check the operation pattern (velocity
monitor). Check the Regeneration
Register load rate and the excessive
regeneration warning, and perform
the following accordingly.
• Increase the capacity of the
Servomotor and Servo Drive.
• Increase the deceleration time.
• Reduce the Servomotor rotation
speed.
• Use an External Regeneration
Resistor.
• Set the Regeneration Resistor
Selection (3016 hex) to 2.
Check the items given for corrections
in advance and implement
countermeasures as required.
This Regeneration Resistor cannot be
used for continuous regenerative
braking. (The operating limit of the
external resistor is limited to a 10%
duty.)
Set the Regeneration Resistor
Selection (3016 hex) to 2.
Set the Regeneration Resistor
Selection (3016 hex) to 2.
Attached
information
None
Precautions/
Remarks
“18” is displayed on the Servo Drive front panel and F018 is given as the AlarmCode (4001 hex)