4.2 Main Commands
72
4.2.15 Release Brake (BRK_OFF: 22H)
BRK_ON and BRK_OFF become always valid as commands unless a warning occurs.
If a BRK_OFF command is sent while power is being supplied to the servomotor, the servo-
motor continues running.
However, if a Servo OFF command is sent later, the brake will remain released because the
BRK_OFF command is valid and may cause a critical situation.
When using a BRK_ON or BRK_OFF command, always keep in mind the status of the com-
mand.
Byte BRK_OFF Description
Command Response
1 22H 22H
Processing clas-
sifications
Control com-
mand group
Synchronization
classifications
Asynchronous
2 − ALARM
Processing time Within commu-
nications cycle
Subcommand Cannot be used
3 STATUS • Turns ON the brake signal and releases the brake.
• Can be used during phases 2 and 3.
• Brake signal output timing
4
5 MONITOR
1
6
7
8
9 MONITOR
2
10
11
12
13 SEL_MON
1/2
SEL_MON
1/2
14 − IO_MON
15
16 WDT RWDT
Within 3 ms
BRK_OFF received
BK
IMPORTANT